ba

en sk

TRI POWER X33 MOD 10 to 60kVA

MODULAR - REDUNDANT - SCALABLE - ADAPTABLE

Tri Power X33 Mod UPS systems operate according to the online double conversion technology (VFI) supporting the load constantly and uninteruptible with pure sine wave voltage. Through the modular power design with either 3.4 or 5 kVA modules a N+X redundancy can be achieved at any time. The low weight of the power modules with 8kg and the modular battery drawers with 13kg allows an easy and cost efficient installation. Malfunctioning modules can be easily swapped and save money on expansive service actions. Backup times up to one hour with modular batteries are possible. Of course for longer backup bigger standard battery banks are available.

Tri Power X33 Mod UPS systems can be used in any critical application in the IT or industrial area and convince with easy handling and operation.

MAIN FEATURES:

- Models: 10 to 60kVA,
- Cost efficient N+X redundancy,
- Customized configuration with 3.4 and 5kVA power modules,
- THDI <3%,
- Modular battery system,
- Easy future power expansion.

REDUNDANT MODULAR ARCHITECTURE

Redundant-modular architecture is the best solution for protecting the vital node points of a company.

ADVANTAGES:

- The powered devices are monitored by a single system,
- Modular expandability,
- Redundant modules,
- Easy maintenance,
- Low running cost,
- Small size.

EFFICIENCY

The UPS in the Tri Power X33 MOD line pay particular attention to both the energy drawn from the network and the power supplied to the user. High Efficiency (>93%), PFC on the Input >0,99, THDI 3%.

ADVANTAGES:

- Increasing the efficiency means reducing that part of the power absorbed by the UPS but not supplied to the load, and tran smitted to the surrounding environment in the form of heat.
- Less heat dispersed in the environment means less need for ventilating or conditioning systems in the installation site.
- A high PFC on the input means doing away with the cost of power factor correction and, thus, increased tariffs.
- There´s no need to oversize a genset (if any) installed on the supply side of the UPS.

EXPANDABILITY

The majority of the UPS systems available on the market are not modular and cannot be expanded. This means that the system must be oversized at the start so as to allow for future expansions (which may not even be required).

ADVANTAGES:

- The Tri Power X33 MOD modular and expandable systems optimize investments in UPS by adapting to the real needs without precluding future expansions and preventing energy from being unnecessarily wasted.
- Increases the efficiency of the system thanks to the right sizing.

RELIABILITY

To obtain a level of redundancy with a conventional UPS at least 2 must be set in parallel, thus doubling the power purchased, the space occupied and the electricity consmptions. Tri Power X33 MOD modular architecture provides redundant configurations in a single cabinet.

ADVANTAGES:

- An UPS with modular redundant architecture can be configured as a power-redundant N+X system. The device will continue to function even if one of the modules is faulty, thus doing away down times.
Clear indications and a generously sized display make faults easy and quick to identify.
- The modular architecture speeds up repairs since the fault module can just be replaced without having to interrupt the service.
- A high percentage of the faults are resolved durring the first assistance intervention.

TECHNICAL SPECIFICATIONS

 Model

X33 Mod 10

X33 Mod 15

X33 Mod 20

X33 Mod 30

X33 Mod 40

X33 Mod 45

X33 Mod 60

 Power (kVA)

10

15

20

30

40

45

60

 INPUT

 Rated voltage

230V 1phase / 400V 3phase +N

400V 3phase +N

 Rated frequency

50Hz / 60Hz

 Power factor
 at full load

>0,99

 THDI

≤3%

 OUTPUT

 Rated power (kVA)

10

15

20

30

40

45

60

 Active power (kW)

8

12

16

24

32

36

48

 UPS Architecture

Modular, Scalable, Redundant N+X with 3400 and 5000VA power modules, housed in one cabinet

 Output power factor

0,8

 Rated voltage

230V 1phase / 400V 3phase +N

400V 3phase +N

 Input/Output
 Configuration

3/3, 3/1, 1/3, 1/1
(user selectable during installation)

3/3

 Static variation

±1%

 Dynamic variation

±3%

 Crest factor

3,5:1

 Voltage distortion

≤1% with linear load / ≤3% with non-linear load

 Frequency

50 Hz / 60 Hz

 Frequency stability
 on battery mode

0,01%

 Overload at pf 0,8

125% for 2 minutes, 150% for 30 seconds

 BATTERIES

 Type

VRLA

ENVIRONMENTAL

 Communication

SNPM slot, 2 x RS232, 1 x Logic interface dry contact port

 Operating
 temperature

0°C - 40°C

 Relative humidity

20% - 80% non condensing

 Noise

At 1 meter distance = 42 - 46 dBA

 Protection rating

IP 20

 Efficiency smart
 mode

Up to 99%

 Weight without
 internal batteries
 (kg)

130

130

154

154-75

154-76

165-75

194-75

 Dimensions HxWxD
 (mm)

414x1645x628

2 x 414x1645x6

 

Tri Power X33 Mod is composed by:

 

Inverter

Power Modules

Battery Drawers

Battery Cabinet