ba

en sk

Serija SCP 35W do 75W with UPS Function (Single Output)

Universal AC input / Full range

Protections: Short circuit / Overload / Over voltage / Battery polarity (by fuse)

Cooling by free air convection

LED indicator for power on

No load power consumption <0,75W

Temperature compensation function (by external thermistor)

100% full load burn-in test

 

 

 

SCP-35
99x97x36mm

SCP-50
129x98x38mm

SCP-75
159x97x38mm

 

AC inrush current: Cold start, 45A

DC adjustment range: 95-115% rated output voltage

Overload protection: 120-165%, hiccup mode, auto-recovery

Over voltage protection: 120-140%, rated output voltage

Setup, rise, hold up time: 500ms, 1200ms, 50ms at full load and 230VAC

Withstand voltage: I/P-O/P: 3kVAC, I/P-FG: 1,5kVAC, 1minute

Working temperature: -20 - +60°C

Safety standard: UL60950-1 approved

Connection: I/P: 3 poles, O/P: 2 poles screw terminal

SCP-35 Series

Model No.

Output

Tol.

R&N

Efficiency

Max.

SCP-35-12

13,8V, 0-2,6A

±2%

120mV

83%

36W

SCP-35-24

27,6V, 0-1,4A

±1%

200mV

86%

39W

SCP-50 Series

Model No.

Output

Tol.

R&N

Efficiency

Max.

SCP-50-12

13,8V, 0-3,6A

±2%

120mV

81%

50W

SCP-50-24

27,6V, 0-1,8A

±1%

200mV

85%

50W

SCP-75 Series

Model No.

Output

Tol.

R&N

Efficiency

Max.

SCP-75-12

13,8V, 0-5,4A

±2%

120mV

81%

75W

SCP-75-24

27,6V, 0-2,7A

±1%

200mV

85%

75W